    Design for · Specification writing

    How do you write an electrical specification that holds up at the bid and at the build?

    Most specifications start as a copy of the last good project. This page shows which lines to fix first, and gives you wording you can lift.

    Ask a question Jump to the lines you can lift

    Design for
    • All guidance
    • Reliability and uptime
    • Build labor
    • Machine data
    • Safety and approvals
    • Environmental responsibility
    • Cost of ownership
    • Panel space
    • Electrical noise (EMC)
    • Specification writing
    9weak lines rewritten so the receiver can check them
    10component sections, each with a line you can lift
    5numbers that set a budget price
    6habits for an approved parts list

    The short answer

    Every line can be checked

    A specification holds up when every line can be checked. State the rating, the listing and the number. Name a brand only as the basis of design. For a budget price, state five numbers and save the component detail for the design stage. Keep approved brands on a separate list with a date and an owner, so the specification does not go stale.

    What it costs when it goes wrong

    For the engineer, the contractor and the owner

    The copied section names a part that changed

    A copied section carries part numbers from the last project. One retired part number stops a submittal and starts a round of questions.

    The brand name has no ratings beside it

    The contractor cannot offer an equal product. The contractor also cannot tell which feature of the brand mattered.

    The word cannot be tested

    Phrases like "industrial rated" and "properly sized" mean something different to each reader. The disagreement shows up at inspection, after the panel is built.

    The number belongs to someone else

    A short-circuit rating with no number makes the panel builder guess. A wrong guess means new parts after the panel is built.

    Weak line, stronger line

    Each weak line below is a kind of line found in real specifications. Each stronger line can be checked by the person who receives it. The square brackets are blanks for your own values.

    The lines on this page are examples for discussion. They are not a specification for any project. The engineer responsible for the project decides what goes in the specification.

    Weak line

    Use Brand X connectors on all panels.

    Stronger line

    Plug and receptacle: [volts] VAC, [amps] A, [poles] pole plus ground, UL Listed. Mechanically interlocked. Lockable in the off position. Basis of design: [make and series]. Equal products are reviewed on the submittal.

    Why it works

    The ratings say what the brand was chosen for. An equal product can be judged against the ratings.

    Weak line

    Only industrial rated hardware is allowed.

    Stronger line

    Components operate from [low] to [high] degrees C. Devices inside the enclosure are finger safe to IP20. Each component carries the listing named in section [number].

    Why it works

    The word "industrial" becomes three things a reviewer can look up.

    Weak line

    DC contactors and breakers must be rated for DC loads.

    Stronger line

    DC contactor: rated at or above [highest system voltage] VDC. Make and break current stated at that voltage. Current direction: [one way or both]. Listing file number on the submittal.

    Why it works

    A DC rating at a lower voltage does not help. The stronger line names the voltage.

    Weak line

    The panel must have an adequate short-circuit current rating.

    Stronger line

    Panel short-circuit current rating: [value] kA at [volts] VAC, marked on the nameplate. Available fault current at the feed: [value] kA, from [study or utility letter], dated [date].

    Why it works

    The panel builder prices the real number. The source and the date show how old the number is.

    Weak line

    Provide current monitoring on each distribution panel.

    Stronger line

    Power meter on each distribution panel: accuracy class [class]. Protocol: [protocol]. Reports kW, kWh, demand, voltage and current for each phase.

    Why it works

    The owner gets the values the owner wanted. A bare current sensor no longer meets the line.

    Weak line

    All components must be UL Listed, not just Recognized, when available.

    Stronger line

    Breakers, disconnects, power supplies and receptacles are UL Listed. Parts sold only as UL Recognized components are accepted inside a UL 508A listed panel, used within the conditions of their recognition.

    Why it works

    The phrase "when available" is gone. The stronger line names the part types that must be Listed.

    Weak line

    Use spring clamp terminals. Avoid screw terminals.

    Stronger line

    Terminal blocks: push-in or spring connection. Wire range, current and voltage shown on the submittal. One ferrule for each connection point on stranded wire. Printed markers.

    Why it works

    The connection type stays. The submittal now has to show the ratings.

    Weak line

    Seal all cable glands to maintain the cabinet rating.

    Stronger line

    Cable entry holds the enclosure at [Type or IP rating]. A split entry is allowed for cables that arrive with connectors fitted. The entry rating is shown on the submittal.

    Why it works

    The rating is named. A cable with a connector already fitted has an allowed way in.

    Weak line

    Size the equipment properly for future expansion.

    Stronger line

    Leave [percent] spare terminals and [percent] free panel space. Size the feed for [percent] added load.

    Why it works

    A person can count spare terminals and measure free space at the factory acceptance test.

    If a line in your specification names a product line we represent, send it to us. We will send the current ratings and the listing file number.

    Five numbers that set a budget price

    An engineer writing for a budget price does not have time to specify every component. In our experience, five numbers move the price more than the component detail does. State the five numbers at the bid, and add the component lines when the job is won.

    1

    System voltage, and AC or DC

    A DC system needs switching and protection parts that are rated for DC at the system voltage.

    2

    Available fault current at the feed

    The available fault current sets the short-circuit rating that every panel on the feed has to meet.

    3

    The environment

    Indoor, outdoor, washdown or hazardous location sets the enclosure, the cable entry and the connectors.

    4

    The listing the inspector will ask for

    A UL 508A listed panel and a panel with no listing are different scopes of work.

    5

    What must be measured and reported

    A revenue-class power meter and a plain current sensor are different equipment.

    These five numbers give a contractor a firmer basis for a budget price. The component lines below fill in the detail at the design stage.

    Lines you can lift

    Power it. Control it. Prove it.

    One tile per component section. Each tile says what to state, gives a sample line with blanks, and names a product we represent for that section. The brand name opens that product line. The lines on this page are examples for discussion. They are not a specification for any project. The engineer responsible for the project decides what goes in the specification.

    Walther interlocked receptacle
    Power it · Walther Electric

    Plugs, receptacles and disconnects

    A cord-connected machine needs a disconnect that the plug cannot defeat.

    State in the line. Voltage, current and poles. The interlock and the lockout. The ingress rating. The listing.

    Sample line. Plug and receptacle: [volts] VAC, [amps] A, [poles] pole plus ground. UL Listed. Mechanically interlocked. Lockable in the off position.

    A product to consider. Walther pin and sleeve, 20 to 100 A, IP44 and IP67, UL Listed and CSA Certified together. On a Walther mechanically interlocked receptacle, the receptacle and the switch are one unit.

    Walther Electric at DynamicStage 02 on the design path

    Schaltbau C310 DC contactor
    Power it · Schaltbau

    DC contactors

    Breaking DC under load is the hard part, so the line has to name the voltage the contactor breaks.

    State in the line. The highest system voltage. Make and break current at that voltage. Current direction. Auxiliary contacts. The listing file number.

    Sample line. DC contactor: rated at or above [volts] VDC. Make and break current stated at that voltage. Current direction: [one way or both]. Listing file number on the submittal.

    A product to consider. Schaltbau C310 and C320 DC contactors are UL Recognized Components to UL 60947-4-1 under file E116641.

    Schaltbau at DynamicStage 07 on the design path

    Premium PSU DPX-240 DIN-rail power supply
    Power it · Premium PSU

    DC power supplies

    The heat a power supply gives off stays in the enclosure, so efficiency belongs in the line.

    State in the line. Input range. Output voltage and current. Efficiency at full load. No-load draw. The listing.

    Sample line. DC power supply: input [range] VAC, output [volts] VDC at [amps] A. Efficiency at least [percent] at full load. Listing: [standard].

    A product to consider. The Premium PSU DPX-240 three-phase supply runs at up to 94.1 percent efficiency and draws 0.8 to 1.1 W at no load.

    Premium PSU at DynamicStage 06 on the design path

    Celduc okpac solid state relay
    Power it · Celduc

    Solid state relays

    A solid state relay is chosen for the load it switches and the temperature inside the panel.

    State in the line. The load type. Load current at the panel temperature. Control voltage. The heat sink.

    Sample line. Solid state relay: [load type] load, [amps] A at [temperature] degrees C inside the panel. Control voltage: [volts]. Heat sink shown on the submittal.

    A product to consider. Celduc 22.5 mm DIN-rail celpac and 45 mm okpac packages, single to four phase, with ready-to-use versions with heatsinks.

    Celduc at DynamicStage 07 on the design path

    IMO UL 489 miniature circuit breaker
    Control it · IMO Automation

    Branch breakers and contactors

    A supplementary protector is not branch circuit protection, so the line names the listing standard.

    State in the line. The listing standard. The current and the trip curve. The interrupt rating at the system voltage.

    Sample line. Branch circuit breaker: UL 489 listed. [amps] A, [curve] trip curve. Interrupt rating at or above [value] kA at [volts] VAC.

    A product to consider. IMO Automation miniature circuit breakers are UL 489 listed, with motor circuit breakers, RCBOs and surge protection in the same catalog.

    IMO Automation at DynamicStage 04 on the design path

    GETT InduSmart panel PC
    Control it · GETT

    Operator keyboards and panel PCs

    The operator station is specified by where it sits and how it gets cleaned.

    State in the line. Screen size. The front ingress rating. Cooling. The operating system. The cleaning method.

    Sample line. Operator panel PC: [size] inch, [rating] front, fanless. Operating system: [system]. Cleaned with [method].

    A product to consider. GETT InduSmart panel PCs from 10.1 to 21.5 inches, IP65 front, fanless, Windows or Linux.

    GETT at DynamicStage 10 on the design path

    SATEC PRO series meter
    Prove it · SATEC

    Power meters

    A meter line with no accuracy class can be met by any current sensor.

    State in the line. The accuracy class. The protocol. The values reported. The current sensor type.

    Sample line. Power meter: accuracy class [class]. Protocol: [protocol]. Reports kW, kWh, demand, voltage and current for each phase.

    A product to consider. SATEC PRO series: a Class 0.2S revenue meter and a Class A Edition 3.1 power quality analyzer in one device.

    SATEC at DynamicStage 03 on the design path

    Brainboxes ED-588 Ethernet remote I/O
    Prove it · Brainboxes

    Remote I/O

    A data line is specified by the signals it reads and the protocol the software polls.

    State in the line. The protocol. Channel count and type. The operating temperature range.

    Sample line. Remote I/O: [number] [type] channels. Protocol: Modbus TCP. Operating range: [low] to [high] degrees C.

    A product to consider. Brainboxes ED Ethernet remote I/O: analog, digital, RTD and thermocouple inputs presented as Modbus TCP devices your own software polls.

    Brainboxes at DynamicStage 11 on the design path

    Walther Electric power distribution assembly
    Foundation · Walther Electric

    Finished power cords and distribution assemblies

    A listed assembly arrives with a label the inspector reads, so the listing question leaves the field.

    State in the line. The length. The connector at each end. The listing of the whole assembly. The test record.

    Sample line. Power cord assembly: [length], with [connector] at each end. Supplied as a UL-listed assembly, labeled, with a test record.

    A product to consider. Walther Electric builds assemblies to length in Somerset, New Jersey as UL-listed assemblies, labeled and 100% tested.

    Walther Electric at DynamicStage 01 on the design path

    Conta-Clip KDS split cable entry frame
    Foundation · Conta-Clip

    Cable entry

    The enclosure rating has to hold where the cables come in.

    State in the line. The enclosure rating to hold. Whether cables arrive with connectors fitted. The entry rating on the submittal.

    Sample line. Cable entry holds the enclosure at [rating]. A split entry is allowed for cables with connectors fitted. The entry rating is shown on the submittal.

    A product to consider. Conta-Clip KDS split cable entry: IP66 and UL Recognized. The KDS passes a cable with its connector on, one frame in place of a row of glands.

    Conta-Clip at DynamicStage 13 on the design path

    For the engineer who keeps the approved parts list

    A factory or a design firm that approves parts for its own projects has the same problem in a different place. These six habits keep an approved parts list useful.

    Keep the requirement and the brand apart

    The specification says what the part must do. The approved parts list says which brands have been checked against the specification.

    Write down why each part is listed

    An approved parts list with reasons can be updated. A list of names gets copied forever.

    Keep two sources where two exist

    A single source puts every project on one manufacturer's lead time.

    Give the list a date and an owner

    Check availability once a year. Remove the part numbers the manufacturer has retired.

    Ask for the listing file number

    A logo on a datasheet cannot be looked up. A listing file number can.

    Publish the path for a new part

    Say what a vendor must send for review: the datasheet, the listing file number and the reason the part is needed.

    Read the detail

    • What is a UL certification and why does it matter?
    • UL 508A complexities and the importance of getting it right
    • UL 489: what it is and how it should be applied
    • NFPA 79: what it is and how it applies to your machine

    See it worked out

    • How a panel's short-circuit rating is set
    • How to read a DC contactor datasheet
    • Panel Wiring Field Guide: ten practices, from layout to the bench check
    • UL 508A Control Panel Compliance Checklist (PDF)

    Data centerBuilding and facilityIndustrial automation

    Go to the product lines

    Walther ElectricSchaltbauPremium PSUCelducIMO AutomationGETTSATECBrainboxesConta-Clip

    Every product line on one page

    Also designing for:

    Cost and total cost of ownershipFootprint and panel spaceEnvironmental responsibilitySafety, approvals and standardsBuild laborReliability and uptimeMachine data

    Questions engineers ask us

    Straight answers on specification writing
    What does "basis of design" mean in an electrical specification?

    Basis of design is the product the engineer designed around. The specification names its make and series, and states the ratings that matter. Another product can be offered when it meets the same ratings. The engineer reviews the other product on the submittal.

    What is the difference between UL Listed and UL Recognized?

    A UL Listed product has been evaluated as a complete product for a stated use. A UL Recognized Component is a building block, evaluated for use inside a listed product such as a UL 508A panel. A specification can say which part types must be Listed, and accept Recognized components inside a listed panel.

    Who provides the short-circuit current number for a control panel?

    The site provides the fault current available where the panel connects. The panel builder then picks parts so the rating marked on the nameplate meets or exceeds the available fault current. Put the number, its source and its date in the specification.

    How do I keep a copied specification from going out of date?

    Give every section a date and an owner. Keep the brands on a separate approved parts list, and check that list once a year. State ratings in the specification, so a retired part number does not make the line wrong.

    Can a manufacturers' rep help with a specification section?

    Yes. Send us the section. For the product lines we represent, we tell you which part numbers the manufacturer has changed. We also send the current datasheets and listing file numbers. The engineer responsible for the project decides the wording.

    Challenge us

    After 30-plus years in the industrial hardware space we know these products, on our line card and off it. Bring us your most stringent or most mundane requirement. If one of our product lines fits, we give you a direct connection to the manufacturer, the right engineer or department, and we stay on your request until it is answered. If it does not, we know someone who will.

    Ask a question Call (408) 780-9190

    Take the line card with you

    Every product line on two pages, in the order a machine gets designed.

    Download the line card (PDF)

    Keep readingDesign guidanceSafety, approvals and standardsPanel Wiring Field GuideThe design pathAll product lines

    Reference use only. Dynamic Measurement & Control Solutions, LLC is a manufacturers' representative. We are not an engineering firm and do not provide professional engineering services. The example lines on this page are for discussion. They are not a specification, a design or installation instructions for any project or site. Product figures are from each maker's published datasheet. This information is provided free and as is. To the fullest extent permitted by law, Dynamic makes no warranty about it and is not liable for any design, specification, installation or result that relies on it.