Design for · Specification writing
Most specifications start as a copy of the last good project. This page shows which lines to fix first, and gives you wording you can lift.
A specification holds up when every line can be checked. State the rating, the listing and the number. Name a brand only as the basis of design. For a budget price, state five numbers and save the component detail for the design stage. Keep approved brands on a separate list with a date and an owner, so the specification does not go stale.
A copied section carries part numbers from the last project. One retired part number stops a submittal and starts a round of questions.
The contractor cannot offer an equal product. The contractor also cannot tell which feature of the brand mattered.
Phrases like "industrial rated" and "properly sized" mean something different to each reader. The disagreement shows up at inspection, after the panel is built.
A short-circuit rating with no number makes the panel builder guess. A wrong guess means new parts after the panel is built.
Each weak line below is a kind of line found in real specifications. Each stronger line can be checked by the person who receives it. The square brackets are blanks for your own values.
The lines on this page are examples for discussion. They are not a specification for any project. The engineer responsible for the project decides what goes in the specification.
Use Brand X connectors on all panels.
Plug and receptacle: [volts] VAC, [amps] A, [poles] pole plus ground, UL Listed. Mechanically interlocked. Lockable in the off position. Basis of design: [make and series]. Equal products are reviewed on the submittal.
The ratings say what the brand was chosen for. An equal product can be judged against the ratings.
Only industrial rated hardware is allowed.
Components operate from [low] to [high] degrees C. Devices inside the enclosure are finger safe to IP20. Each component carries the listing named in section [number].
The word "industrial" becomes three things a reviewer can look up.
DC contactors and breakers must be rated for DC loads.
DC contactor: rated at or above [highest system voltage] VDC. Make and break current stated at that voltage. Current direction: [one way or both]. Listing file number on the submittal.
A DC rating at a lower voltage does not help. The stronger line names the voltage.
The panel must have an adequate short-circuit current rating.
Panel short-circuit current rating: [value] kA at [volts] VAC, marked on the nameplate. Available fault current at the feed: [value] kA, from [study or utility letter], dated [date].
The panel builder prices the real number. The source and the date show how old the number is.
Provide current monitoring on each distribution panel.
Power meter on each distribution panel: accuracy class [class]. Protocol: [protocol]. Reports kW, kWh, demand, voltage and current for each phase.
The owner gets the values the owner wanted. A bare current sensor no longer meets the line.
All components must be UL Listed, not just Recognized, when available.
Breakers, disconnects, power supplies and receptacles are UL Listed. Parts sold only as UL Recognized components are accepted inside a UL 508A listed panel, used within the conditions of their recognition.
The phrase "when available" is gone. The stronger line names the part types that must be Listed.
Use spring clamp terminals. Avoid screw terminals.
Terminal blocks: push-in or spring connection. Wire range, current and voltage shown on the submittal. One ferrule for each connection point on stranded wire. Printed markers.
The connection type stays. The submittal now has to show the ratings.
Seal all cable glands to maintain the cabinet rating.
Cable entry holds the enclosure at [Type or IP rating]. A split entry is allowed for cables that arrive with connectors fitted. The entry rating is shown on the submittal.
The rating is named. A cable with a connector already fitted has an allowed way in.
Size the equipment properly for future expansion.
Leave [percent] spare terminals and [percent] free panel space. Size the feed for [percent] added load.
A person can count spare terminals and measure free space at the factory acceptance test.
If a line in your specification names a product line we represent, send it to us. We will send the current ratings and the listing file number.
An engineer writing for a budget price does not have time to specify every component. In our experience, five numbers move the price more than the component detail does. State the five numbers at the bid, and add the component lines when the job is won.
A DC system needs switching and protection parts that are rated for DC at the system voltage.
The available fault current sets the short-circuit rating that every panel on the feed has to meet.
Indoor, outdoor, washdown or hazardous location sets the enclosure, the cable entry and the connectors.
A UL 508A listed panel and a panel with no listing are different scopes of work.
A revenue-class power meter and a plain current sensor are different equipment.
These five numbers give a contractor a firmer basis for a budget price. The component lines below fill in the detail at the design stage.
One tile per component section. Each tile says what to state, gives a sample line with blanks, and names a product we represent for that section. The brand name opens that product line. The lines on this page are examples for discussion. They are not a specification for any project. The engineer responsible for the project decides what goes in the specification.

A cord-connected machine needs a disconnect that the plug cannot defeat.
State in the line. Voltage, current and poles. The interlock and the lockout. The ingress rating. The listing.
Sample line. Plug and receptacle: [volts] VAC, [amps] A, [poles] pole plus ground. UL Listed. Mechanically interlocked. Lockable in the off position.
A product to consider. Walther pin and sleeve, 20 to 100 A, IP44 and IP67, UL Listed and CSA Certified together. On a Walther mechanically interlocked receptacle, the receptacle and the switch are one unit.

Breaking DC under load is the hard part, so the line has to name the voltage the contactor breaks.
State in the line. The highest system voltage. Make and break current at that voltage. Current direction. Auxiliary contacts. The listing file number.
Sample line. DC contactor: rated at or above [volts] VDC. Make and break current stated at that voltage. Current direction: [one way or both]. Listing file number on the submittal.
A product to consider. Schaltbau C310 and C320 DC contactors are UL Recognized Components to UL 60947-4-1 under file E116641.

The heat a power supply gives off stays in the enclosure, so efficiency belongs in the line.
State in the line. Input range. Output voltage and current. Efficiency at full load. No-load draw. The listing.
Sample line. DC power supply: input [range] VAC, output [volts] VDC at [amps] A. Efficiency at least [percent] at full load. Listing: [standard].
A product to consider. The Premium PSU DPX-240 three-phase supply runs at up to 94.1 percent efficiency and draws 0.8 to 1.1 W at no load.

A solid state relay is chosen for the load it switches and the temperature inside the panel.
State in the line. The load type. Load current at the panel temperature. Control voltage. The heat sink.
Sample line. Solid state relay: [load type] load, [amps] A at [temperature] degrees C inside the panel. Control voltage: [volts]. Heat sink shown on the submittal.
A product to consider. Celduc 22.5 mm DIN-rail celpac and 45 mm okpac packages, single to four phase, with ready-to-use versions with heatsinks.

A supplementary protector is not branch circuit protection, so the line names the listing standard.
State in the line. The listing standard. The current and the trip curve. The interrupt rating at the system voltage.
Sample line. Branch circuit breaker: UL 489 listed. [amps] A, [curve] trip curve. Interrupt rating at or above [value] kA at [volts] VAC.
A product to consider. IMO Automation miniature circuit breakers are UL 489 listed, with motor circuit breakers, RCBOs and surge protection in the same catalog.

The operator station is specified by where it sits and how it gets cleaned.
State in the line. Screen size. The front ingress rating. Cooling. The operating system. The cleaning method.
Sample line. Operator panel PC: [size] inch, [rating] front, fanless. Operating system: [system]. Cleaned with [method].
A product to consider. GETT InduSmart panel PCs from 10.1 to 21.5 inches, IP65 front, fanless, Windows or Linux.

A meter line with no accuracy class can be met by any current sensor.
State in the line. The accuracy class. The protocol. The values reported. The current sensor type.
Sample line. Power meter: accuracy class [class]. Protocol: [protocol]. Reports kW, kWh, demand, voltage and current for each phase.
A product to consider. SATEC PRO series: a Class 0.2S revenue meter and a Class A Edition 3.1 power quality analyzer in one device.

A data line is specified by the signals it reads and the protocol the software polls.
State in the line. The protocol. Channel count and type. The operating temperature range.
Sample line. Remote I/O: [number] [type] channels. Protocol: Modbus TCP. Operating range: [low] to [high] degrees C.
A product to consider. Brainboxes ED Ethernet remote I/O: analog, digital, RTD and thermocouple inputs presented as Modbus TCP devices your own software polls.

A listed assembly arrives with a label the inspector reads, so the listing question leaves the field.
State in the line. The length. The connector at each end. The listing of the whole assembly. The test record.
Sample line. Power cord assembly: [length], with [connector] at each end. Supplied as a UL-listed assembly, labeled, with a test record.
A product to consider. Walther Electric builds assemblies to length in Somerset, New Jersey as UL-listed assemblies, labeled and 100% tested.

The enclosure rating has to hold where the cables come in.
State in the line. The enclosure rating to hold. Whether cables arrive with connectors fitted. The entry rating on the submittal.
Sample line. Cable entry holds the enclosure at [rating]. A split entry is allowed for cables with connectors fitted. The entry rating is shown on the submittal.
A product to consider. Conta-Clip KDS split cable entry: IP66 and UL Recognized. The KDS passes a cable with its connector on, one frame in place of a row of glands.
A factory or a design firm that approves parts for its own projects has the same problem in a different place. These six habits keep an approved parts list useful.
The specification says what the part must do. The approved parts list says which brands have been checked against the specification.
An approved parts list with reasons can be updated. A list of names gets copied forever.
A single source puts every project on one manufacturer's lead time.
Check availability once a year. Remove the part numbers the manufacturer has retired.
A logo on a datasheet cannot be looked up. A listing file number can.
Say what a vendor must send for review: the datasheet, the listing file number and the reason the part is needed.
Walther ElectricSchaltbauPremium PSUCelducIMO AutomationGETTSATECBrainboxesConta-Clip
Every product line on one page
Also designing for:
Cost and total cost of ownershipFootprint and panel spaceEnvironmental responsibilitySafety, approvals and standardsBuild laborReliability and uptimeMachine data
Basis of design is the product the engineer designed around. The specification names its make and series, and states the ratings that matter. Another product can be offered when it meets the same ratings. The engineer reviews the other product on the submittal.
A UL Listed product has been evaluated as a complete product for a stated use. A UL Recognized Component is a building block, evaluated for use inside a listed product such as a UL 508A panel. A specification can say which part types must be Listed, and accept Recognized components inside a listed panel.
The site provides the fault current available where the panel connects. The panel builder then picks parts so the rating marked on the nameplate meets or exceeds the available fault current. Put the number, its source and its date in the specification.
Give every section a date and an owner. Keep the brands on a separate approved parts list, and check that list once a year. State ratings in the specification, so a retired part number does not make the line wrong.
Yes. Send us the section. For the product lines we represent, we tell you which part numbers the manufacturer has changed. We also send the current datasheets and listing file numbers. The engineer responsible for the project decides the wording.
After 30-plus years in the industrial hardware space we know these products, on our line card and off it. Bring us your most stringent or most mundane requirement. If one of our product lines fits, we give you a direct connection to the manufacturer, the right engineer or department, and we stay on your request until it is answered. If it does not, we know someone who will.
Every product line on two pages, in the order a machine gets designed.
Reference use only. Dynamic Measurement & Control Solutions, LLC is a manufacturers' representative. We are not an engineering firm and do not provide professional engineering services. The example lines on this page are for discussion. They are not a specification, a design or installation instructions for any project or site. Product figures are from each maker's published datasheet. This information is provided free and as is. To the fullest extent permitted by law, Dynamic makes no warranty about it and is not liable for any design, specification, installation or result that relies on it.