Pin and sleeve connectors, interlocked receptacles, finished cable assemblies and the distribution boxes that feed them. Most 30, 60 and 100 A drops in a North American data center end in an IEC 60309 device, and Walther builds the whole run from the plug to the box above the rack, with the assemblies built in Somerset, New Jersey.
Dynamic is the Walther rep for Northern California and Northern Nevada, working with the electrical contractors building data centers, the distributors who stock for them, and the engineers who write the drop schedule.
Cross-reference a part numberSend us your drop schedule
Drops arrive with the plugs landed, the cable cut to length and the listing carried by the assembly, so fit-out stays off the field-labor budget and the inspector sees one listed part. Adapter plates fit the back boxes already on the wall.
Data center contractor line cardStock the dual-rated number and cross the industry number at the counter with the table below. When a contractor needs finished drops built to a schedule, we quote it through the factory and stay on it to delivery.
Part number cross referenceConnectors short formSettle the rating, the ground clock position and the listing path before the one-line locks. Adding drops in a live data center becomes a plug-in job, not a termination job in the rack row.
Data centers and digital infrastructureData center line cardWalther builds the power path to the rack: the receptacle on the wall, the finished drop, the splitter and the distribution box above the rack.
Plugs, connectors, receptacles and appliance inlets from 20 to 100 A. The housing color marks the voltage and the ground pin's clock position keys it, so a 480 V plug cannot mate with a 208 V receptacle.
The receptacle and the switch built as one part. The plug cannot go in or come out while the circuit is live, and the switch locks out in the off position, so connect, disconnect and lockout happen at one device.
The plug, the cable and the termination arrive as one finished assembly built to the drop schedule: plug on end 1, termination on end 2, cable type and length. Listed as an assembly, so the listing rides with the drop and not just the parts.
Distribution that brings 30, 60 and 100 A to the point of use. The rack distribution box sits above the rack and splits one 60 A feed into three 30 A outputs. Portable boxes carry internal breaker protection, and custom boxes are built to spec.
The drawing names an industry part number. Find its row, read across to the Walther IP67 or IP44 number for the same plug, connector, receptacle or inlet. IEC 60309 devices interchange with any conforming maker, so the Walther part mates with what is already installed. Same ground clock position, same voltage.
Jump to 16 A 30 A 60 A 100 A · Download Walther's cross reference (PDF)
| Voltage AC | Ground clock | Poles | Plug | Connector | Receptacle | Inlet | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Industry no. | Walther IP67 | Walther IP44 | Industry no. | Walther IP67 | Walther IP44 | Industry no. | Walther IP67 | Walther IP44 | Industry no. | Walther IP67 | Walther IP44 | |||
| 16/20 A | ||||||||||||||
| 200-250 V | 6 | 2P + G | 320P6 | 219306 | 211306 or 210306 | 320C6 | 319306 | 311306 or 310306 | 320R6 | 419306 | 410306 | 320B6 | 619306 | 615306 |
| 480 V | 7 | 2P + G | 320P7 | 219319 | 211319 or 210319 | 320C7 | 319319 | 311319 or 310319 | 320R7 | 419319 | 410319 | 320B7 | 619319 | 615319 |
| 380-415 V | 6 | 3P + G | 416P6 | 219406 | 210406 | 416C6 | 319406 | 310406 | 416R6 | 419406 | 410406 | 416B6 | 619406 | 615406 |
| 200-250 V | 9 | 3P + G | 420P9 | 219409 | 212409 or 210409 | 420C9 | 319409 | 312409 or 310409 | 420R9 | 419409 | 410409 | 420B9 | 619409 | 615409 |
| 3 phase 480 V | 7 | 3P + G | 420P7 | 218419 | 212419 or 210419 | 420C7 | 318419 | 312419 or 310419 | 420R7 | 419419 | 410419 | 420B7 | 619419 | 615419 |
| 200/346 V, 240/415 V | 6 | 3P + N + G | 520P6 | 219 | 210 or 211 | 520C6 | 319 | 310 or 311 | 520R6 | 419 | 410 | 520B6 | 619 | 615 |
| 120/208 V | 9 | 3P + N + G | 520P9 | 219509 | 212509 or 210509 | 520C9 | 319509 | 312509 or 310509 | 520R9 | 419509 | 410509 | 520B9 | 619509 | 615509 |
| 3 phase 277/480 V | 7 | 3P + N + G | 520P7 | 218519 | 212519 or 210519 | 520C7 | 318519 | 312519 or 310519 | 520R7 | 419519 | 410519 | 520B7 | 619519 | 615519 |
| 30/32 A | ||||||||||||||
| 200-250 V | 6 | 2P + G | 330P6 | 239306 | 230306 | 330C6 | 339306 | 330306 | 330R6 | 439306 | 430306 | 330B6 | 639306 | 635306 |
| 480 V | 7 | 2P + G | 330P7 | 239319 | 230319 | 330C7 | 339319 | 330319 | 330R7 | 439319 | 430319 | 330B7 | 639319 | 635319 |
| 380-415 V | 6 | 3P + G | 432P6 | 239406 | 230406 | 432C6 | 339406 | 330406 | 432R6 | 439406 | 430406 | 432B6 | 639406 | 635406 |
| 200-250 V | 9 | 3P + G | 430P9 | 239409 | 230409 | 430C9 | 339409 | 330409 | 430R9 | 439409 | 430409 | 430B9 | 639409 | 635409 |
| 3 phase 480 V | 7 | 3P + G | 430P7 | 238419 | 232419 or 230419 | 430C7 | 338419 | 332419 or 330419 | 430R7 | 439419 | 430419 | 430B7 | 639419 | 635419 |
| 200/346 V, 240/415 V | 6 | 3P + N + G | 530P6 | 239 | 230 (10 AWG) or 232 (8 AWG) | 530C6 | 339 | 330 (10 AWG) or 332 (8 AWG) | 530R6 | 439 | 430 | 530B6 | 639 | 635 |
| 120/208 V | 9 | 3P + N + G | 530P9 | 239509 | 230509 | 530C9 | 339509 | 330509 | 530R9 | 439509 | 430509 | 530B9 | 639509 | 635509 |
| 3 phase 277/480 V | 7 | 3P + N + G | 530P7 | 238519 | 232519 or 230519 | 530C7 | 338519 | 332519 or 330519 | 530R7 | 439519 | 430519 | 530B7 | 639519 | 635519 |
| 60/63 A | ||||||||||||||
| 200-250 V | 6 | 2P + G | 360P6 | 269306 | 261306 or 260306 | 360C6 | 369306 | 361306 or 360306 | 360R6 | 469306 | 460306 | 360B6 | 669306 | 665306 |
| 480 V | 7 | 2P + G | 360P7 | 269319 | 261319 or 260319 | 360C7 | 369319 | 361319 or 360319 | 360R7 | 469319 | 460319 | 360B7 | 669319 | 665319 |
| 380-415 V | 6 | 3P + G | 463P6 | 269406 | 261406 or 260406 | 463C6 | 369406 | 361406 or 360406 | 463R6 | 469406 | 460406 | 463B6 | 669406 | 665406 |
| 200-250 V | 9 | 3P + G | 460P9 | 269409 | 261409 or 260409 | 460C9 | 369409 | 361409 or 360409 | 460R9 | 469409 | 460409 | 460B9 | 669409 | 665409 |
| 3 phase 480 V | 7 | 3P + G | 460P7 | 269419 | 261419 or 260419 | 460C7 | 369419 | 361419 or 360419 | 460R7 | 469419 | 460419 | 460B7 | 669419 | 665419 |
| 200/346 V, 240/415 V | 6 | 3P + N + G | 560P6 | 269 | 261 or 260 | 560C6 | 369 | 361 or 360 | 560R6 | 469 | 460 | 560B6 | 669 | 665 |
| 120/208 V | 9 | 3P + N + G | 560P9 | 269509 | 261509 or 260509 | 560C9 | 369509 | 361509 or 360509 | 560R9 | 469509 | 460509 | 560B9 | 669509 | 665509 |
| 3 phase 277/480 V | 7 | 3P + N + G | 560P7 | 269519 | 261519 or 260519 | 560C7 | 369519 | 361519 or 360519 | 560R7 | 469519 | 460519 | 560B7 | 669519 | 665519 |
| 100/125 A | ||||||||||||||
| 200-250 V | 6 | 2P + G | 3100P6W | 279318 | IP67 only | 3100C6W | 379318 | IP67 only | 3100R6W | 479318 | IP67 only | 3100B6W | 679318 | IP67 only |
| 480 V | 7 | 2P + G | 3100P7W | 279319 | IP67 only | 3100C7W | 379319 | IP67 only | 3100R7W | 479319 | IP67 only | 3100B7W | 679319 | IP67 only |
| 380-415 V | 6 | 3P + G | 4125P6W | 279406 | IP67 only | 4100C6W | 379406 | IP67 only | 4100R6W | 479406 | IP67 only | 4100B6W | 679406 | IP67 only |
| 200-250 V | 9 | 3P + G | 4100P9W | 279421 | IP67 only | 4100C9W | 379421 | IP67 only | 4100R9W | 479421 | IP67 only | 4100B9W | 679421 | IP67 only |
| 3 phase 480 V | 7 | 3P + G | 4100P7W | 279419 | IP67 only | 4100C7W | 379419 | IP67 only | 4100R7W | 479419 | IP67 only | 4100B7W | 679419 | IP67 only |
| 200/346 V, 240/415 V | 6 | 3P + N + G | 5100P6W | 279 | IP67 only | 5100C6W | 379 | IP67 only | 5100R6W | 479 | IP67 only | 5100B6W | 679 | IP67 only |
| 120/208 V | 9 | 3P + N + G | 5100P9W | 279521 | IP67 only | 5100C9W | 379521 | IP67 only | 5100R9W | 479521 | IP67 only | 5100B9W | 679521 | IP67 only |
| 3 phase 277/480 V | 7 | 3P + N + G | 5100P7W | 279519 | IP67 only | 5100C7W | 379519 | IP67 only | 5100R7W | 479519 | IP67 only | 5100B7W | 679519 | IP67 only |
Voltage colors follow Walther's flyer. Ratings read North American / IEC (for example 30/32 A). On the 30 A five-wire row, 232 and 332 carry a larger backshell for 8 AWG SOO cable. Where two IP44 numbers are shown, Walther lists both for the same device. 100/125 A devices are IP67 only. Transcribed from Walther's cross reference, rev 2202; we confirm the part number and listing on every quote.
IEC 60309 is the international standard for industrial plugs, sockets and couplers. The housing color marks the voltage and the position of the ground pin, read like a clock face, keys the device, so a plug cannot mate with a receptacle of a different voltage or configuration. In North America the Series II devices are rated 20, 30, 60 and 100 A.
Yes. IEC 60309 devices interchange with any conforming maker's device of the same rating, voltage and ground clock position. The cross reference on this page reads an industry part number across to the Walther IP67 or IP44 number for the same plug, connector, receptacle or inlet.
IP44 devices are splash-proof for indoor and covered locations. IP67 devices are watertight against temporary immersion, for washdown floors, outdoor sites and anywhere a hose or rain reaches the connector. Walther makes both versions across plugs, connectors, receptacles and inlets.
A finished drop arrives with the plug landed, the cable cut to length and the termination built, and it is listed as an assembly, so the inspector sees one listed part and the fit-out stays off the field-labor budget. Walther builds them to the drop schedule in Somerset, New Jersey, at 30, 60 and 100 A.
It is a receptacle and a switch built as one part. The plug cannot be inserted or removed while the circuit is live, and the switch locks out in the off position, so connecting, disconnecting and lockout happen at one device. Versions with a breaker cover branches that need their own protection.
Walther pin and sleeve devices are dual rated, UL Listed and CSA Certified together, so one part number covers a US or a Canadian job. We confirm the part number and the listing for your device on every quote.
Dynamic Measurement and Control Solutions is the Walther Electric representative for Northern California and Northern Nevada. Send the drop schedule or the part numbers on the drawing, and we come back with the Walther numbers or a quote on the finished drops.
See every line in design order on the design path, or the whole line card on the products page.
Procon heavy-duty rectangular connectors · Manual disconnect switches · Remote access interface ports · Liquid-tight dome connectors · Custom power distribution
Available through us on request. Ask about any of them with your next drop schedule.
Answer what you can. Only email is required, and a drop schedule or the part numbers on the drawing help most.