    Panel Wiring Field Guide · DC measurement

    How to read a DC transducer accuracy spec

    Every DC current or voltage sensor comes with an accuracy number, such as 0.5 percent. The number only helps once you know what it is a percent of. On most data sheets it is a percent of the largest value the sensor can measure. That makes it a fixed amount of error, and a fixed amount of error matters more and more as the signal gets smaller. This guide explains how to read the accuracy section of a data sheet, and how to work out what the error will be at low current, where most measurement problems show up.

    Inside

    1. 1Why small DC signals are hard to measure
    2. 2Percent of reading and percent of full scale
    3. 3Reading the accuracy lines
    4. 4Working out the error at 100, 10 and 1 percent of range
    5. 5The shunt, and the small voltages around it
    6. 6The bus voltage and the measurement
    7. 7Fit the range to the signal
    8. 8Installation
    9. 9The Knick figures, as printed on the data sheets

    Who it is for

    Engineers who measure current and voltage on battery, storage, charger, traction, electrolyzer and 800 VDC systems, and the panel shops that wire the measuring point.

    It is the companion to How to read a DC contactor datasheet in the Panel Wiring Field Guide.

    1Why small DC signals are hard to measure

    Most DC systems run far below their rated current most of the time. A battery string built to deliver 2,000 A may sit at a few amps for hours. A charger slows down as the battery fills. A bus that carries thousands of amps under load can sit near zero while a fault is starting. So a current measurement has to be right at a few amps and at full current.

    At low current the signal is very small. Current on a DC bus is usually measured with a shunt. A shunt is a precise resistor placed in the bus. Current flowing through it produces a small voltage, and a device called a transducer reads that voltage and sends a signal to the controller. A common shunt produces 60 millivolts at its full rated current. At 1 percent of rated current the same shunt produces 600 microvolts, which is less than a thousandth of a volt. That tiny voltage sits on a bus that may be hundreds or thousands of volts above ground.

    DC bus at high voltagecurrentShuntA small voltage:60 mV at rated current,600 microvolts at 1 percentTransducerbus sideat bus voltagecontrol sideat groundisolation barrierController4 to 20 mA or 10 V
    The measuring chain, from the bus to the controller.

    DC also takes away a tool that AC measurements rely on. An AC signal changes direction many times a second. Any steady error in the electronics does not change, so it can be filtered out. A DC signal is steady, and so are the errors. A small error in the amplifier, a small voltage created where two metals touch, and a slow drift as the cabinet warms up all look exactly like real current. Once they are mixed in, nothing can separate them.

    Four things decide how good a low-current DC measurement is:

    • The fixed errors inside the transducer.
    • Small voltages created by heat at the wire connections.
    • The high voltage of the bus itself, which can leak into the reading.
    • How well the measuring range matches the real signal.

    The rest of this guide takes these one at a time.

    2Percent of reading and percent of full scale

    An accuracy number is always a percent of something. Data sheets use two different meanings, and the difference is the most important thing on the page.

    Percent of reading. Some sheets print it as "of measured value". The error is a percent of whatever the sensor is measuring right now. Say the accuracy is 0.1 percent of reading. The error is 0.1 percent of the signal at full current. It is still 0.1 percent of the signal at a hundredth of full current. The error shrinks along with the signal.

    Percent of full scale. Full scale means the largest value the sensor is built to measure. Sheets also print it as "of range", "of span", "of nominal" or "F.S." Here the error is a fixed amount that does not shrink. For example, 0.25 percent of full scale on a 60 millivolt input is 150 microvolts. That 150 microvolts of possible error is there at full current, and it is still there when the signal has dropped to almost nothing.

    A sensor rated 0.25 percent of full scale, 60 mV input.The possible error is always 150 microvolts.Signal at full range: 60 mV0.25 percentof the readingSignal at one tenth: 6 mV2.5 percentof the readingSignal at one hundredth: 0.6 mV25 percentof the readingthe readingthe possible error, as a share of the reading
    A fixed error becomes a larger share of the reading as the current drops.

    A fixed error is small next to a large signal and large next to a small one. The table shows how the same full scale accuracy looks as the signal drops.

    How much of the range the signal is usingError from a sensor rated 0.25 percent of full scaleError from a sensor rated 1 percent of full scale
    All of it (100 percent)0.25 percent of the reading1 percent of the reading
    Half (50 percent)0.5 percent2 percent
    One tenth (10 percent)2.5 percent10 percent
    One hundredth (1 percent)25 percent100 percent

    The numbers in this table are simple arithmetic. They come from dividing the fixed error by the signal, and they apply to any sensor specified this way.

    If a data sheet prints an accuracy number and does not say what it is a percent of, assume full scale until the maker confirms otherwise. Makers of laboratory meters handle this by printing both parts: a percent of reading plus a percent of range. That is the clearest way to state accuracy, and it is the pattern to look for on a transducer data sheet too.

    3Reading the accuracy lines

    A good data sheet does not give one accuracy number. It lists several separate sources of error, each on its own line. Here is what each line means. The examples are from the Knick P41000, a transducer that reads the small voltage from a shunt.

    Gain error. This is an error in the scale of the measurement, like a ruler that is very slightly too long. It is always the same percent of the reading. The P41000 data sheet prints "Gain error < 0.1 % of measured value". The Knick P42000, which measures bus voltage, prints under 0.3 percent of measured value, with 0.1 percent available as an option.

    Offset error. This is the small output the transducer gives when the input is exactly zero, like a bathroom scale that shows half a pound with nobody on it. It is a fixed amount. The P41000 and P42000 manuals print "Offset error < 20 µA or 10 mV" at the output. On a standard 20 mA or 10 V output signal, that works out to 0.1 percent of the full output. If a data sheet lists a gain error and no offset error, ask the maker what the offset is.

    Gain errorinputoutputOffset errorinputoutputoutput at zeroidealwith the error
    Gain error changes the slope. Offset error shifts the whole line. Both are exaggerated here.

    Linearity. This describes how closely the output follows a straight line between zero and full scale. Some sheets include it in the main accuracy number and say so. Others state it only for part of the range, for example from 10 to 100 percent of full scale. In that case the sheet promises nothing below 10 percent.

    Temperature coefficient. This tells you how much the error grows as the cabinet warms up. The P41000 manual prints under 0.005 percent of full scale for each kelvin of temperature change, as an average, measured from 23 C. A kelvin is the same size as a degree Celsius. If the cabinet runs 20 degrees warmer than that, the added error can be up to 0.1 percent of full scale. Check whether a sheet's accuracy number applies at one temperature or across the whole operating range.

    Common-mode rejection (CMRR). This describes how well the transducer keeps the high bus voltage out of the reading. On a shunt measurement it is one of the most important lines on the data sheet. Section 6 of this guide explains it with an example

    Response time and cutoff frequency. These tell you how quickly the output follows a sudden change. The P41000 prints a response time of about 110 microseconds to reach 90 percent of a step, and a cutoff frequency of about 5 kHz. A transducer that takes hundreds of milliseconds to respond is averaging the signal. Averaging smooths out noise, and it also smooths out the fast event you may need to see.

    Reference conditions. These are the temperature, supply voltage and load at which the printed numbers are true. If an accuracy number comes with no conditions, treat it as typical performance and not as a limit.

    4Working out the error at 100, 10 and 1 percent of range

    Section 3 listed the separate errors. To find the total error for your system, add them together at the current your system actually runs at, and not only at full current.

    The table below does this for three kinds of data sheet. The first two give a single full scale number. The third gives a gain error and an offset error separately, using the Knick P41000 figures from section 3. In each case the errors are simply added, which is the worst case, at the reference temperature.

    What the data sheet saysError when using all of the rangeError at one tenth of the rangeError at one hundredth of the range
    1 percent of full scale1 percent of the reading10 percent100 percent
    0.25 percent of full scale0.25 percent2.5 percent25 percent
    0.1 percent of reading, plus an offset of 0.1 percent of the full output (the P41000)0.2 percent1.1 percent10.1 percent

    At full current the three sensors look about the same. At one tenth of the range, the sensor in the third row is two to nine times better than the other two. At one hundredth of the range it is still the best of the three, and the reading could still be off by about 10 percent.

    That last point is worth saying plainly. No transducer makes a very small signal easy to measure. Any fixed error, however small, becomes a large share of a tiny signal.

    There is one more thing to look for on a data sheet. Some sheets state their main accuracy number only at the rated value. Some state it "excluding offset". Either one means the number was never meant to describe low current. The offset, linearity and temperature lines further down the sheet describe that, and you have to add them yourself.

    This is why it pays to do the arithmetic before choosing a part. It is also why the measuring range matters as much as the accuracy number. Section 7 explains how to choose the range.

    Keep two things in mind about the table. First, it adds up worst-case limits, and a real part usually performs better than its limits. Second, it covers only the transducer. The shunt, the wire connections and the bus voltage each add some error of their own. The next two sections cover those.

    5The shunt, and the small voltages around it

    A shunt turns bus current into millivolts. The class on its label tells you how close its resistance is to the stated value.
    A shunt turns bus current into millivolts. The class on its label tells you how close its resistance is to the stated value.Photo: Knick

    As section 1 explained, a shunt is a precise resistor placed in the bus. It turns current into a small voltage, usually between 30 and 100 millivolts at rated current. Four things about the shunt affect the measurement.

    Accuracy class. The class tells you how close the shunt's resistance is to its stated value, at the reference temperature. Knick offers shunts in class 0.2 and class 0.5, which means within 0.2 or 0.5 percent. They cover 1 A to 20 kA, with 30 mV and 60 mV as the standard output voltages. An error in resistance behaves like the gain error in section 3. It stays the same percent of the reading at any current. So the shunt is rarely what causes trouble at low current.

    Heating. A shunt warms up as it carries current, and its resistance changes slightly with temperature. Knick makes the resistor element from manganin, an alloy chosen because its resistance changes very little. The Knick data sheet prints a change of 0.1 percent for every 10 degrees on a class 0.2 shunt. On a class 0.5 shunt it is 0.25 percent for every 10 degrees. To keep the heating down, shunt makers, Knick Interface among them, recommend running a shunt at no more than two thirds of its rated current when the current is continuous. Choose a shunt large enough that your continuous current stays at or below two thirds of its rating.

    Where the measuring wires connect. A shunt has two small screw terminals called voltage taps, separate from the large bolts that carry the bus current. The taps are positioned so that only the voltage across the precise resistor is measured. Always connect the measuring wires to these taps, and never under the large bolts. If the measuring wires pick up any of the copper that carries the bus current, the resistance of that copper is added to the measurement. Copper's resistance changes with temperature hundreds of times more than the shunt alloy does, so the reading would drift as the bus warms up.

    resistor elementbus boltbus boltvoltage tapsConnect the measuring wires to the twosmall voltage taps. Twist the pair.Never under a bus bolt. The copper thereadds resistance that drifts with heat.
    Where the measuring wires connect on a shunt.

    Voltages created by heat. Wherever two different metals touch, a small voltage appears that depends on temperature. This is how a thermocouple works. A copper wire on a manganin shunt produces about 1 microvolt for each degree, according to the alloy maker's data. A shunt has two measuring connections. If both are at the same temperature, the two small voltages cancel out. If one end of the shunt runs 5 degrees hotter than the other, about 5 microvolts is left over. At full current, 5 microvolts against 60 millivolts does not matter. At 1 percent of rated current the signal is only 600 microvolts, and 5 microvolts is nearly 1 percent of the reading. A corroded connection is far worse. Published measurement handbooks put copper against copper oxide at around 1,000 microvolts for each degree.

    In practice this comes down to four habits when wiring a shunt. Use clean copper wire to the voltage taps. Make both connections the same way. Keep both connections at the same temperature. Avoid adding any other joints between different metals in the measuring wires.

    6The bus voltage and the measurement

    A shunt sits directly in the bus. That means both of its measuring wires are at the full bus voltage. The transducer has to measure a difference of a few millivolts between two wires that are both hundreds or thousands of volts above the ground of the control system.

    Engineers call that shared voltage the common-mode voltage. A small part of it always leaks into the reading. How small is given by a number on the data sheet called the common-mode rejection ratio, or CMRR, measured in decibels (dB). A higher number is better. Every extra 20 dB means ten times less leakage.

    Both wires from the shunt are at the bus voltage.wire 1: 1,000 V above groundwire 2: 1,000.06 V above groundTransducerreads the differencesignalThe difference, 60 mV, is the signal you want.The shared 1,000 V is the common-mode voltage.The transducer has to ignore it.At 150 dB of rejection, about 32 microvolts still gets through.
    Millivolts between two wires that are both at bus voltage.

    Here is an example for a 1,000 V bus and a 60 millivolt shunt. The table shows how much error leaks in at three levels of rejection.

    Common-mode rejection on the data sheetError that leaks into the measurementCompared with the signal at full current (60 millivolts)Compared with the signal at 1 percent current (600 microvolts)
    100 dB10 mV17 percentmore than the signal
    120 dB1 mV1.7 percentmore than the signal
    150 dBabout 32 microvolts0.05 percentabout 5 percent

    These numbers are arithmetic from the definition of the ratio. They show why a transducer for shunt measurement on a high-voltage bus needs a very high rejection figure. The Knick P41000 manual prints approximately 150 dB at DC on input ranges up to 1 V. Knick's shunt data sheet makes the same point in words: measuring low shunt voltages without distortion, especially 30 mV, needs a transducer with a higher common-mode rejection ratio.

    Two related points are worth knowing. First, a steady leak from the bus voltage looks just like the offset error from section 3, so it is easy to blame the wrong part. Second, the bus voltage is rarely steady. Each time a power converter switches, the bus voltage jumps very quickly. How well a transducer rejects those fast jumps is a separate line on the data sheet. The P41000 prints approximately 115 dB for a 1,000 V jump that rises in 1 microsecond.

    Rejection is one half of the job. Isolation is the other half. The working voltage rating on the data sheet tells you the transducer can safely sit at bus voltage all the time. The rejection figure tells you the reading stays accurate while it does. A simple resistor divider, or a low-voltage amplifier placed in front of a controller input, provides neither one.

    7Fit the range to the signal

    Knick P42000 voltage transducer. The range is ordered to match the bus.
    Knick P42000 voltage transducer. The range is ordered to match the bus.Photo: Knick

    Sections 2 and 4 showed that fixed errors are a percent of the measuring range. So the simplest way to reduce them is to choose a range that is no larger than you need.

    Here is an example. Suppose a transducer is ordered with a 0 to 60 millivolt input, and it is connected to a shunt that never produces more than 20 millivolts. Two thirds of the range is never used. Every fixed error is three times larger, compared with the signal, than it needs to be. The same thing happens with a voltage transducer set for 0 to 1,500 V on a bus that runs at 800 V.

    Range ordered: 0 to 60 mVSignal never above 20 mV: two thirds is unused.fixed errorThe fixed error is a share of the full 60 mV.Range ordered: 0 to 20 mVThe signal uses the whole range.fixed errorThe same share of 20 mV is one third the size.the signal, inside the rangefixed error (enlarged to show)
    Order the range to match the real signal.

    Three choices help.

    • Order the input range to match the real signal. Knick calibrates the P41000 to the range you order, anywhere from 50 mV to 100 V, with 30 mV on request. The P42000 can be ordered from 100 V to 3,600 V. Some models carry up to 16 calibrated ranges that can be selected with switches, so a change during commissioning needs no recalibration.
    • Choose the shunt voltage with low current in mind. A 60 mV shunt gives twice the signal of a 30 mV shunt at every current. The small errors from heat and bus voltage stay the same, so they matter half as much. The cost is that a 60 mV shunt also produces twice the heat. Which one is better depends on where your system spends most of its time.
    • Use a two-direction output when current flows both ways. A battery bus both charges and discharges. An output of plus and minus 10 V, or plus and minus 20 mA, puts zero current at zero output. The offset error can then be read directly whenever no current is flowing.

    After choosing the range, go back to section 4 and work out the error again using the range you actually ordered.

    8Installation

    Knick P41000 shunt transducer. It mounts in the control cabinet.
    Knick P41000 shunt transducer. It mounts in the control cabinet.Photo: Knick

    Many low-current measurement errors come from how the parts are wired, and not from the parts themselves. These practices come from the Knick manuals and from the effects described in sections 5 and 6.

    • Twist the two measuring wires together, and keep them twisted until they are close to the terminals. The P41000 manual gives this instruction. Two wires that are spread apart form a loop, and a loop picks up interference from the switching current in the bus beside it.
    • Use copper wire only, as the P41000 data sheet says, and make both measuring connections the same way. Section 5 explains why.
    • Keep the measuring wires short and away from power cables. Where they have to cross a power cable, cross at a right angle.
    • Connect to the shunt's voltage taps, and keep both taps at the same temperature. Avoid having one tap next to a hot joint or in the air stream from a fan.
    • Mount the transducer inside the control cabinet, as the manual requires. The shunt itself is bare metal at bus voltage, and its data sheet rates it IP00, which means it has no protection against touch. It belongs behind a barrier.
    • Choose a shunt with room to spare for continuous current, and give it free air to cool.
    • Record the zero reading. With the bus live and no current flowing, the output shows the total of all the fixed errors in the measurement. Write that number in the commissioning record. It is the first thing to check if anyone questions a reading later.

    9The Knick figures, as printed on the data sheets

    This table collects the accuracy figures used in this guide, as Knick prints them in its current data sheets and manuals. The exact value depends on the model and the options ordered. Check the data sheet for the exact part number before putting a figure on a drawing.

    PartWhat it measuresGain errorOffset errorChange with temperatureOther figures that matter at low signal
    P41000Shunt voltage and other small voltages on a high-voltage bus, 50 mV to 100 V inputsUnder 0.1 percent of measured valueUnder 20 µA or 10 mV at the outputUnder 0.005 percent of full scale per kelvinCommon-mode rejection approx. 150 dB at DC; response time approx. 110 microseconds
    P42000Bus voltage, 100 V to 3,600 V inputsUnder 0.3 percent of measured value; 0.1 percent optionalUnder 20 µA or 10 mV at the outputUnder 0.01 percent of full scale per kelvinResponse time approx. 110 microseconds
    P29000Voltage up to 1,000 V, and millivolt inputs from 20 mV0.1 percent of measured value on inputs up to 1 V; 0.2 percent above 1 V0.1 percent of full scaleUnder 50 ppm of full scale per kelvin up to 1 V; under 80 ppm per kelvin aboveZero can be adjusted by up to 5 percent
    P45000Stack and bus voltage up to 3,000 V0.2 percent of the measured value at 23 C; 0.1 percent optional on versions without SIL capabilitySee the data sheetSee the data sheetSettling time under 70 microseconds
    ShuntsCurrent from 1 A to 20 kA, 30 mV and 60 mV standardClass 0.2 or class 0.5 at 23 CNone, because a shunt is a plain resistor0.1 percent per 10 K (class 0.2); 0.25 percent per 10 K (class 0.5)Manganin resistor element; M5 voltage taps

    Working voltage is a separate question from accuracy. P41000 and P42000 models built with one fixed range are rated for a working voltage of 3,600 V AC or DC. Models with switchable ranges are rated for 2,200 V. Both ratings cover an 800 VDC or a 1,500 VDC bus.

    No data sheet, from Knick or anyone else, prints one accuracy number for a small signal. The number for your measurement comes from adding up the pieces covered in this guide: the gain error, the offset error, the temperature effect, the shunt class, and the range you chose.

    Specifying the measuring point

    The selection starts with five numbers:

    • The bus voltage.
    • The rated current.
    • The lowest current that still has to be measured, and how accurate it has to be at that current.
    • How fast the signal has to respond.
    • The kind of signal the controller accepts, such as 4 to 20 mA or 0 to 10 V.

    Two more details help: the temperature around the shunt, and whether current flows in both directions. With these in hand, the range, the shunt and the transducer can be chosen, and the expected error can be written down before anything is ordered.

    Choosing a DC transducer or a shunt? Have those numbers in hand, and we help you specify it.

    Knick Interface transducers and shunts: https://www.dynamicrep.com/knick-interface

    Sources

    Manufacturer data (data sheets of record)

    • Knick, ProLine P41000 data sheet TB-253.106-KNEN01 (2026-04-20) and user manual TA-253.106-KNEN06 (Version 6, 2023-04-20): input ranges, gain error, offset error, temperature coefficient, common-mode rejection, response time, wiring notes.
    • Knick, ProLine P42000 data sheet TB-253.107-KNEN01 (2026-04-20) and user manual TA-253.107-KNEN06.
    • Knick, VariTrans P29000 data sheet and user manual 086100 (Version 3.0, 2019).
    • Knick, P45000 data sheet TB-257.500-KNEN02 (2025-05-20).
    • Knick, "Shunt Resistor for Direct Current Measurements from 1 A to 20 kA", data sheet TB-300.641-KNEN04 (2026-04-28): accuracy classes, rated drops, manganin, temperature coefficient, IEC 60051-8 reference conditions.
    • Knick Interface, KI series shunt sheet (2018): the two-thirds continuous loading recommendation.
    • Isabellenhuette, MANGANIN precision alloy data sheet (October 2022): thermal EMF against copper, temperature coefficient of resistance.

    Measurement practice

    • Keithley, "Low Level Measurements Handbook", 7th edition: percent of reading and percent of range, offset as the dominant term at low readings, thermoelectric EMF table, noise rejection in decibels.
    • Texas Instruments, application note SBOA562, "Using Current Sense Amplifiers at Near-Zero Vsense": offset error at small sense voltages.

    Standards (summarized, never reproduced)

    • IEC 60051-1 and IEC 60051-8 (accuracy classes and reference conditions for shunts), as cited on the Knick shunt data sheet.
    • EN 61010-1 and EN 50124-1 (working voltage and insulation coordination), as cited in the Knick P40000 series documents.