Every DC current or voltage sensor comes with an accuracy number, such as 0.5 percent. The number only helps once you know what it is a percent of. On most data sheets it is a percent of the largest value the sensor can measure. That makes it a fixed amount of error, and a fixed amount of error matters more and more as the signal gets smaller. This guide explains how to read the accuracy section of a data sheet, and how to work out what the error will be at low current, where most measurement problems show up.
Engineers who measure current and voltage on battery, storage, charger, traction, electrolyzer and 800 VDC systems, and the panel shops that wire the measuring point.
It is the companion to How to read a DC contactor datasheet in the Panel Wiring Field Guide.
Most DC systems run far below their rated current most of the time. A battery string built to deliver 2,000 A may sit at a few amps for hours. A charger slows down as the battery fills. A bus that carries thousands of amps under load can sit near zero while a fault is starting. So a current measurement has to be right at a few amps and at full current.
At low current the signal is very small. Current on a DC bus is usually measured with a shunt. A shunt is a precise resistor placed in the bus. Current flowing through it produces a small voltage, and a device called a transducer reads that voltage and sends a signal to the controller. A common shunt produces 60 millivolts at its full rated current. At 1 percent of rated current the same shunt produces 600 microvolts, which is less than a thousandth of a volt. That tiny voltage sits on a bus that may be hundreds or thousands of volts above ground.
DC also takes away a tool that AC measurements rely on. An AC signal changes direction many times a second. Any steady error in the electronics does not change, so it can be filtered out. A DC signal is steady, and so are the errors. A small error in the amplifier, a small voltage created where two metals touch, and a slow drift as the cabinet warms up all look exactly like real current. Once they are mixed in, nothing can separate them.
Four things decide how good a low-current DC measurement is:
The rest of this guide takes these one at a time.
An accuracy number is always a percent of something. Data sheets use two different meanings, and the difference is the most important thing on the page.
Percent of reading. Some sheets print it as "of measured value". The error is a percent of whatever the sensor is measuring right now. Say the accuracy is 0.1 percent of reading. The error is 0.1 percent of the signal at full current. It is still 0.1 percent of the signal at a hundredth of full current. The error shrinks along with the signal.
Percent of full scale. Full scale means the largest value the sensor is built to measure. Sheets also print it as "of range", "of span", "of nominal" or "F.S." Here the error is a fixed amount that does not shrink. For example, 0.25 percent of full scale on a 60 millivolt input is 150 microvolts. That 150 microvolts of possible error is there at full current, and it is still there when the signal has dropped to almost nothing.
A fixed error is small next to a large signal and large next to a small one. The table shows how the same full scale accuracy looks as the signal drops.
| How much of the range the signal is using | Error from a sensor rated 0.25 percent of full scale | Error from a sensor rated 1 percent of full scale |
|---|---|---|
| All of it (100 percent) | 0.25 percent of the reading | 1 percent of the reading |
| Half (50 percent) | 0.5 percent | 2 percent |
| One tenth (10 percent) | 2.5 percent | 10 percent |
| One hundredth (1 percent) | 25 percent | 100 percent |
The numbers in this table are simple arithmetic. They come from dividing the fixed error by the signal, and they apply to any sensor specified this way.
If a data sheet prints an accuracy number and does not say what it is a percent of, assume full scale until the maker confirms otherwise. Makers of laboratory meters handle this by printing both parts: a percent of reading plus a percent of range. That is the clearest way to state accuracy, and it is the pattern to look for on a transducer data sheet too.
A good data sheet does not give one accuracy number. It lists several separate sources of error, each on its own line. Here is what each line means. The examples are from the Knick P41000, a transducer that reads the small voltage from a shunt.
Gain error. This is an error in the scale of the measurement, like a ruler that is very slightly too long. It is always the same percent of the reading. The P41000 data sheet prints "Gain error < 0.1 % of measured value". The Knick P42000, which measures bus voltage, prints under 0.3 percent of measured value, with 0.1 percent available as an option.
Offset error. This is the small output the transducer gives when the input is exactly zero, like a bathroom scale that shows half a pound with nobody on it. It is a fixed amount. The P41000 and P42000 manuals print "Offset error < 20 µA or 10 mV" at the output. On a standard 20 mA or 10 V output signal, that works out to 0.1 percent of the full output. If a data sheet lists a gain error and no offset error, ask the maker what the offset is.
Linearity. This describes how closely the output follows a straight line between zero and full scale. Some sheets include it in the main accuracy number and say so. Others state it only for part of the range, for example from 10 to 100 percent of full scale. In that case the sheet promises nothing below 10 percent.
Temperature coefficient. This tells you how much the error grows as the cabinet warms up. The P41000 manual prints under 0.005 percent of full scale for each kelvin of temperature change, as an average, measured from 23 C. A kelvin is the same size as a degree Celsius. If the cabinet runs 20 degrees warmer than that, the added error can be up to 0.1 percent of full scale. Check whether a sheet's accuracy number applies at one temperature or across the whole operating range.
Common-mode rejection (CMRR). This describes how well the transducer keeps the high bus voltage out of the reading. On a shunt measurement it is one of the most important lines on the data sheet. Section 6 of this guide explains it with an example
Response time and cutoff frequency. These tell you how quickly the output follows a sudden change. The P41000 prints a response time of about 110 microseconds to reach 90 percent of a step, and a cutoff frequency of about 5 kHz. A transducer that takes hundreds of milliseconds to respond is averaging the signal. Averaging smooths out noise, and it also smooths out the fast event you may need to see.
Reference conditions. These are the temperature, supply voltage and load at which the printed numbers are true. If an accuracy number comes with no conditions, treat it as typical performance and not as a limit.
Section 3 listed the separate errors. To find the total error for your system, add them together at the current your system actually runs at, and not only at full current.
The table below does this for three kinds of data sheet. The first two give a single full scale number. The third gives a gain error and an offset error separately, using the Knick P41000 figures from section 3. In each case the errors are simply added, which is the worst case, at the reference temperature.
| What the data sheet says | Error when using all of the range | Error at one tenth of the range | Error at one hundredth of the range |
|---|---|---|---|
| 1 percent of full scale | 1 percent of the reading | 10 percent | 100 percent |
| 0.25 percent of full scale | 0.25 percent | 2.5 percent | 25 percent |
| 0.1 percent of reading, plus an offset of 0.1 percent of the full output (the P41000) | 0.2 percent | 1.1 percent | 10.1 percent |
At full current the three sensors look about the same. At one tenth of the range, the sensor in the third row is two to nine times better than the other two. At one hundredth of the range it is still the best of the three, and the reading could still be off by about 10 percent.
That last point is worth saying plainly. No transducer makes a very small signal easy to measure. Any fixed error, however small, becomes a large share of a tiny signal.
There is one more thing to look for on a data sheet. Some sheets state their main accuracy number only at the rated value. Some state it "excluding offset". Either one means the number was never meant to describe low current. The offset, linearity and temperature lines further down the sheet describe that, and you have to add them yourself.
This is why it pays to do the arithmetic before choosing a part. It is also why the measuring range matters as much as the accuracy number. Section 7 explains how to choose the range.
Keep two things in mind about the table. First, it adds up worst-case limits, and a real part usually performs better than its limits. Second, it covers only the transducer. The shunt, the wire connections and the bus voltage each add some error of their own. The next two sections cover those.

As section 1 explained, a shunt is a precise resistor placed in the bus. It turns current into a small voltage, usually between 30 and 100 millivolts at rated current. Four things about the shunt affect the measurement.
Accuracy class. The class tells you how close the shunt's resistance is to its stated value, at the reference temperature. Knick offers shunts in class 0.2 and class 0.5, which means within 0.2 or 0.5 percent. They cover 1 A to 20 kA, with 30 mV and 60 mV as the standard output voltages. An error in resistance behaves like the gain error in section 3. It stays the same percent of the reading at any current. So the shunt is rarely what causes trouble at low current.
Heating. A shunt warms up as it carries current, and its resistance changes slightly with temperature. Knick makes the resistor element from manganin, an alloy chosen because its resistance changes very little. The Knick data sheet prints a change of 0.1 percent for every 10 degrees on a class 0.2 shunt. On a class 0.5 shunt it is 0.25 percent for every 10 degrees. To keep the heating down, shunt makers, Knick Interface among them, recommend running a shunt at no more than two thirds of its rated current when the current is continuous. Choose a shunt large enough that your continuous current stays at or below two thirds of its rating.
Where the measuring wires connect. A shunt has two small screw terminals called voltage taps, separate from the large bolts that carry the bus current. The taps are positioned so that only the voltage across the precise resistor is measured. Always connect the measuring wires to these taps, and never under the large bolts. If the measuring wires pick up any of the copper that carries the bus current, the resistance of that copper is added to the measurement. Copper's resistance changes with temperature hundreds of times more than the shunt alloy does, so the reading would drift as the bus warms up.
Voltages created by heat. Wherever two different metals touch, a small voltage appears that depends on temperature. This is how a thermocouple works. A copper wire on a manganin shunt produces about 1 microvolt for each degree, according to the alloy maker's data. A shunt has two measuring connections. If both are at the same temperature, the two small voltages cancel out. If one end of the shunt runs 5 degrees hotter than the other, about 5 microvolts is left over. At full current, 5 microvolts against 60 millivolts does not matter. At 1 percent of rated current the signal is only 600 microvolts, and 5 microvolts is nearly 1 percent of the reading. A corroded connection is far worse. Published measurement handbooks put copper against copper oxide at around 1,000 microvolts for each degree.
In practice this comes down to four habits when wiring a shunt. Use clean copper wire to the voltage taps. Make both connections the same way. Keep both connections at the same temperature. Avoid adding any other joints between different metals in the measuring wires.
A shunt sits directly in the bus. That means both of its measuring wires are at the full bus voltage. The transducer has to measure a difference of a few millivolts between two wires that are both hundreds or thousands of volts above the ground of the control system.
Engineers call that shared voltage the common-mode voltage. A small part of it always leaks into the reading. How small is given by a number on the data sheet called the common-mode rejection ratio, or CMRR, measured in decibels (dB). A higher number is better. Every extra 20 dB means ten times less leakage.
Here is an example for a 1,000 V bus and a 60 millivolt shunt. The table shows how much error leaks in at three levels of rejection.
| Common-mode rejection on the data sheet | Error that leaks into the measurement | Compared with the signal at full current (60 millivolts) | Compared with the signal at 1 percent current (600 microvolts) |
|---|---|---|---|
| 100 dB | 10 mV | 17 percent | more than the signal |
| 120 dB | 1 mV | 1.7 percent | more than the signal |
| 150 dB | about 32 microvolts | 0.05 percent | about 5 percent |
These numbers are arithmetic from the definition of the ratio. They show why a transducer for shunt measurement on a high-voltage bus needs a very high rejection figure. The Knick P41000 manual prints approximately 150 dB at DC on input ranges up to 1 V. Knick's shunt data sheet makes the same point in words: measuring low shunt voltages without distortion, especially 30 mV, needs a transducer with a higher common-mode rejection ratio.
Two related points are worth knowing. First, a steady leak from the bus voltage looks just like the offset error from section 3, so it is easy to blame the wrong part. Second, the bus voltage is rarely steady. Each time a power converter switches, the bus voltage jumps very quickly. How well a transducer rejects those fast jumps is a separate line on the data sheet. The P41000 prints approximately 115 dB for a 1,000 V jump that rises in 1 microsecond.
Rejection is one half of the job. Isolation is the other half. The working voltage rating on the data sheet tells you the transducer can safely sit at bus voltage all the time. The rejection figure tells you the reading stays accurate while it does. A simple resistor divider, or a low-voltage amplifier placed in front of a controller input, provides neither one.

Sections 2 and 4 showed that fixed errors are a percent of the measuring range. So the simplest way to reduce them is to choose a range that is no larger than you need.
Here is an example. Suppose a transducer is ordered with a 0 to 60 millivolt input, and it is connected to a shunt that never produces more than 20 millivolts. Two thirds of the range is never used. Every fixed error is three times larger, compared with the signal, than it needs to be. The same thing happens with a voltage transducer set for 0 to 1,500 V on a bus that runs at 800 V.
Three choices help.
After choosing the range, go back to section 4 and work out the error again using the range you actually ordered.

Many low-current measurement errors come from how the parts are wired, and not from the parts themselves. These practices come from the Knick manuals and from the effects described in sections 5 and 6.
This table collects the accuracy figures used in this guide, as Knick prints them in its current data sheets and manuals. The exact value depends on the model and the options ordered. Check the data sheet for the exact part number before putting a figure on a drawing.
| Part | What it measures | Gain error | Offset error | Change with temperature | Other figures that matter at low signal |
|---|---|---|---|---|---|
| P41000 | Shunt voltage and other small voltages on a high-voltage bus, 50 mV to 100 V inputs | Under 0.1 percent of measured value | Under 20 µA or 10 mV at the output | Under 0.005 percent of full scale per kelvin | Common-mode rejection approx. 150 dB at DC; response time approx. 110 microseconds |
| P42000 | Bus voltage, 100 V to 3,600 V inputs | Under 0.3 percent of measured value; 0.1 percent optional | Under 20 µA or 10 mV at the output | Under 0.01 percent of full scale per kelvin | Response time approx. 110 microseconds |
| P29000 | Voltage up to 1,000 V, and millivolt inputs from 20 mV | 0.1 percent of measured value on inputs up to 1 V; 0.2 percent above 1 V | 0.1 percent of full scale | Under 50 ppm of full scale per kelvin up to 1 V; under 80 ppm per kelvin above | Zero can be adjusted by up to 5 percent |
| P45000 | Stack and bus voltage up to 3,000 V | 0.2 percent of the measured value at 23 C; 0.1 percent optional on versions without SIL capability | See the data sheet | See the data sheet | Settling time under 70 microseconds |
| Shunts | Current from 1 A to 20 kA, 30 mV and 60 mV standard | Class 0.2 or class 0.5 at 23 C | None, because a shunt is a plain resistor | 0.1 percent per 10 K (class 0.2); 0.25 percent per 10 K (class 0.5) | Manganin resistor element; M5 voltage taps |
Working voltage is a separate question from accuracy. P41000 and P42000 models built with one fixed range are rated for a working voltage of 3,600 V AC or DC. Models with switchable ranges are rated for 2,200 V. Both ratings cover an 800 VDC or a 1,500 VDC bus.
No data sheet, from Knick or anyone else, prints one accuracy number for a small signal. The number for your measurement comes from adding up the pieces covered in this guide: the gain error, the offset error, the temperature effect, the shunt class, and the range you chose.
The selection starts with five numbers:
Two more details help: the temperature around the shunt, and whether current flows in both directions. With these in hand, the range, the shunt and the transducer can be chosen, and the expected error can be written down before anything is ordered.
Choosing a DC transducer or a shunt? Have those numbers in hand, and we help you specify it.