To measure current on a high-voltage DC bus, put a shunt in the bus and read it with a transducer that sits at bus potential and isolates the signal. To measure the bus voltage, use a voltage transducer rated for the bus itself. Both hand the controller a standard 4 to 20 mA or 10 V signal that is safe to wire into a panel.
The isolation is the whole job. The measurement is small. The voltage it rides on is not.
On an AC system, current transformers and voltage transformers do the isolating. They are simple, proven and everywhere.
Neither works on DC. A DC bus has no zero crossing, and a transformer cannot pass a steady current. So ripple, unbalance and ground faults on a DC bus go unmeasured unless something is built to read them at high potential.
That matters more each year. Battery storage, traction power and the 800 VDC bus in new data centers all put kilovolt DC where a controller needs a reading.
The difficulty is where it sits. The shunt is on the bus, so its millivolt signal rides on top of the full bus voltage. The transducer mounts beside the shunt at bus potential, reads the millivolts, and passes an isolated signal across to the controller.
Knick's P41000 does this job. It takes shunt inputs from 50 mV to 100 V, with a gain error under 0.1 percent and a working voltage of 3,600 V. Knick's shunts run from 1 A to 20 kA.
The shunt and the transducer input sit at bus potential. Only the isolated signal crosses to the control side.
Knick's P42000 takes inputs from 100 V to 3,600 V across 16 calibrated, switchable ranges, with a gain error under 0.3 percent. For systems built to a safety integrity level, the P45000 takes inputs to 3,000 V with reinforced insulation to 4,800 V, and is built for SIL 2 systems.
A hot joint on a busbar is a fault that has not happened yet. A Pt100 sensor clamped to the joint reads the hot spot, with the sensor at bus potential and the output isolated from it. Knick's P44000 takes a Pt100 input with isolation to 2,000 V or 6,600 V.
Knick transducers are made in Berlin and supported from Knick Interface in California. At Dynamic we represent Knick Interface in Northern California and Northern Nevada. Send us the measuring point: the position on the bus, the voltage and current rating, and what the signal reports to. We will work the selection with you and with Knick.
The Knick Interface page has the full range. For power from the same bus, see how to get 24 V control power and AC from a high-voltage DC bus
At Dynamic we represent power, control and measurement lines for machine builders, panel shops and plants in Northern California and Northern Nevada, and we represent Knick Interface across the territory.