Branch Circuit Monitoring: How to Meter Many Circuits in One Panel

Written by Jeff Weseloh | Nov 20, 2026, 4:00:00 PM

Branch circuit monitoring gives each circuit in a panel its own reading of current, power and energy. The practical way to cover many circuits is one multi-circuit meter in the panel, fed by a current sensor on each circuit. One SATEC BFM-II meters up to 54 single-phase or 18 three-phase circuits from a single DIN rail unit.

That replaces a row of separate meters with one device and one data connection to the building or plant system.

Why meter by branch circuit

A main meter shows what the whole building or plant drew. It does not show which load drew it.

Metering by branch circuit splits that total into the loads behind it. Ovens, chillers, compressed air and each production line get their own kWh. A production run then has a cost, and an idle week has a number.

In a data center, the same idea covers the PDU and panelboard circuits that feed each row.

Energy codes ask for a load breakout too. The code depends on the building: Title 24 Part 6 section 130.5 in California, the 2021 IECC section C405.12 in Nevada, and ASHRAE 90.1 section 8.4.3 for federal and out-of-state work. This article on energy code submetering covers what each one asks for.

One meter for many circuits

A multi-circuit meter has many current inputs and one set of voltage inputs. Each current input reads the sensor on one conductor.

One BFM-II meters up to 54 single-phase circuits or 18 three-phase circuits. It mounts on DIN rail in the panel the contractor is already building. It talks Modbus or BACnet, so the readings land in the building or plant system the operators already use.

Virtual channels add circuits together. Several circuits that feed one load category can be totaled into the figure a code report or a cost report asks for.

A panel fed from two voltage sources needs the BFM-II voltage input module. With that module, the unit handles 36 current channels.

 

How to plan it, step by step

  1. List the circuits that matter. Start from the panel schedule. Mark the large loads and the ones someone will ask about.
  2. Count single-phase and three-phase circuits. The count sets how many multi-circuit meters the panel needs.
  3. Check the voltage sources. One source per meter is the simple case. Two sources need the voltage input module.
  4. Size the current sensors. Each sensor is sized to its conductor and its current.
  5. Pick solid-core or split-core sensors. The accuracy section below explains the choice.
  6. Find the space. A DIN rail position in the panel, or a small enclosure nearby. HACS sensor leads run up to 650 feet (200 m), so the meter can sit away from the panel it measures.
  7. Decide where the data goes. Modbus or BACnet to the building or plant system, and the register list that system needs.

Accuracy belongs to the whole chain

A meter's accuracy class only holds if the sensors in front of it hold it too. A Class 0.2S meter reading through a 1 percent current transformer is a 1 percent system.

HACS sensors feed the SATEC meter directly, so the chain has one sensor in it instead of two.

On the BFM-II, the class holds at 0.5S with solid-core HACS sensors. With split-core sensors it is Class 1.

Split-core sensors suit an existing panel. HACS split-core sensors open and close around the existing conductor and feed the meter directly with no shorting blocks, so nothing is cut or re-terminated. A qualified electrician installs them with the circuit de-energized, which keeps the outage to a short planned window.

Energy by circuit, power quality at the service

The BFM-II gives each circuit its load and its energy. A sag that trips a machine, or harmonics from a drive, are a job for a SATEC PRO Series meter or a PM17x PRO analyzer at the service or the feeder.

A common layout is one analyzer where the power comes in and multi-circuit meters on the panels below it. This article on power meters and power quality analyzers explains the difference.

What drives the cost

  • Circuit count. It sets how many multi-circuit meters the job needs.
  • The sensors. One per conductor, sized to it, solid-core or split-core.
  • Installation. A short planned outage per panel to fit the sensors.
  • Integration. SATEC's PAS software ships with every instrument at no charge. Mapping the readings into a building or plant system takes configuration at that end.

Questions engineers ask

How many circuits can one meter cover?

One BFM-II covers up to 54 single-phase or 18 three-phase circuits from a single voltage source.

Does it connect to a building automation system?

Yes. The BFM-II talks Modbus or BACnet.

Can it go into an existing panel?

Yes. Split-core sensors fit around the existing conductors. The circuit is de-energized while they go in, in a short planned window.

Can it total circuits for an energy code report?

Yes. Virtual channels add circuits into the load categories a code asks for. Which code applies depends on the building.

How it is bought and who supports it here