Branch circuit monitoring gives each circuit in a panel its own reading of current, power and energy. The practical way to cover many circuits is one multi-circuit meter in the panel, fed by a current sensor on each circuit. One SATEC BFM-II meters up to 54 single-phase or 18 three-phase circuits from a single DIN rail unit.
That replaces a row of separate meters with one device and one data connection to the building or plant system.
A main meter shows what the whole building or plant drew. It does not show which load drew it.
Metering by branch circuit splits that total into the loads behind it. Ovens, chillers, compressed air and each production line get their own kWh. A production run then has a cost, and an idle week has a number.
In a data center, the same idea covers the PDU and panelboard circuits that feed each row.
Energy codes ask for a load breakout too. The code depends on the building: Title 24 Part 6 section 130.5 in California, the 2021 IECC section C405.12 in Nevada, and ASHRAE 90.1 section 8.4.3 for federal and out-of-state work. This article on energy code submetering covers what each one asks for.
One BFM-II meters up to 54 single-phase circuits or 18 three-phase circuits. It mounts on DIN rail in the panel the contractor is already building. It talks Modbus or BACnet, so the readings land in the building or plant system the operators already use.
Virtual channels add circuits together. Several circuits that feed one load category can be totaled into the figure a code report or a cost report asks for.
A panel fed from two voltage sources needs the BFM-II voltage input module. With that module, the unit handles 36 current channels.
A meter's accuracy class only holds if the sensors in front of it hold it too. A Class 0.2S meter reading through a 1 percent current transformer is a 1 percent system.
HACS sensors feed the SATEC meter directly, so the chain has one sensor in it instead of two.
On the BFM-II, the class holds at 0.5S with solid-core HACS sensors. With split-core sensors it is Class 1.
Split-core sensors suit an existing panel. HACS split-core sensors open and close around the existing conductor and feed the meter directly with no shorting blocks, so nothing is cut or re-terminated. A qualified electrician installs them with the circuit de-energized, which keeps the outage to a short planned window.
The BFM-II gives each circuit its load and its energy. A sag that trips a machine, or harmonics from a drive, are a job for a SATEC PRO Series meter or a PM17x PRO analyzer at the service or the feeder.
A common layout is one analyzer where the power comes in and multi-circuit meters on the panels below it. This article on power meters and power quality analyzers explains the difference.
One BFM-II covers up to 54 single-phase or 18 three-phase circuits from a single voltage source.
Yes. The BFM-II talks Modbus or BACnet.
Yes. Split-core sensors fit around the existing conductors. The circuit is de-energized while they go in, in a short planned window.
Yes. Virtual channels add circuits into the load categories a code asks for. Which code applies depends on the building.
Dynamic is the SATEC rep for Northern California and Northern Nevada. Send us the panel schedule and what each circuit needs to tell you. We will work out the meter and sensor list with you and with SATEC.
To find the loads behind a demand charge, see how to find which machines drive your plant demand charge. The SATEC page has the full range of meters and analyzers.
At Dynamic we represent power, control and measurement lines for machine builders, panel shops and plants in Northern California and Northern Nevada, and we are SATEC's rep across the territory.